Replace the SAS Cable
This is an internal component that is accessible from the back of the
server by removing the SMOD. Perform this procedure to replace the SAS cable
on the SMODs.
-
Prepare the server for cold service.
This is a cold-service component. Power down the system and disconnect
the AC power cables from the server before performing this
procedure.
See Preparing the Server for Component Replacement.
-
Remove the SMOD.
See Remove an SMOD.
-
Set the SMOD on a flat surface with the front side facing toward
you.
-
Close the SMOD handles.
-
Rotate the SMOD 180 degrees so the back (connector) side is facing
toward you.
-
Turn the SMOD upside down and locate the HBA.
The HBA card is located inside the SMOD.
Note -
The connector (back) side of the SMOD should still be facing you.
-
Disconnect the SAS cable from the HBA port [1].
-
Disconnect the SAS cable from the drive backplane [2].
-
Carefully route the SAS cable away from the guide.
-
Remove the SAS cable from the SMOD.
-
Connect the replacement Mini-SAS4I cable end labeled "TO DBP" to the
drive backplane.
-
Route the replacement SAS cable from the drive backplane to the HBA
card connector.
-
Ensure that the cable is routed under the support bracket.
-
Connect the replacement Mini-SAS4I cable end labeled "TO HBA" to the
HBA card connector.
-
Install the SMOD.
See Install an SMOD.
-
Prepare the server for operation.
See Returning the Server to Operation.